ACTIVE LENGTH OF THE CABLE LINES WITH AN UINSULATED METAL SHEATH FROM THE STANDPOINT OF GROUNDING EFFECTS CONFERENCE EUROCON2009

机译:从接地效果会议Eurocon2009的接地效果的角度,电缆线的电缆线的主动长度

获取原文

摘要

It is well known that the MV paper-insulated cables lines act as long grounding electrodes, or inject fault current directly into the surrounding soil. As a consequence of that the MV lines performed of this type of cables spontaneously form a very large and complex grounding system around the HV/MV distribution substations. The area encompassed by this type of grounding system is much larger than occupied by the HV/MV substation itself. Because of that these grounding systems manifest excellent performances including a very low value of the impedance to ground. The problem with this type of grounding systems appears only at the design stage of the HV/MV substation, when safety condition inside and in the vicinity of this substation should be estimated. This paper provides improvements in accuracy to the only existing practical method developed for the analysis of this type of grounding systems.
机译:众所周知,MV纸绝缘电缆线用作长接地电极,或将故障电流直接注入到周围的土壤中。因此,通过对这种类型的电缆进行的MV线自发地形成围绕HV / MV分配变电站非常大而复杂的接地系统。这种类型的接地系统所包括的区域远大于HV / MV变电站本身的占用。因此,这些接地系统表现出优异的性能,包括对地阻抗的非常低的值。这种类型的接地系统的问题仅在HV / MV变电站的设计阶段出现,当时应估计该变电站附近和附近的安全条件。本文对唯一用于分析这种接地系统的现有实用方法提供了改进。