摘要

The introduction of Distributed Generation (DG) into distribution networks has a significant effect on losses. This effect can be detrimental or beneficial depending on where DG units are allocated and which sizes they have. This paper deals with optimal siting and sizing of DG units for minimizing the total power losses in a radial distribution network under bidirectional and unidirectional power flow scenario. An Enhanced Genetic Algorithm (EGA) is used for effectively explore the problem search space. Moreover, a simple and straightforward penalty function is presented in which the normalization of the violations is not needed. The method is implemented and tested on a typical 16-bus distribution network. Simulation results indicate that unidirectional flow constraint may restricts the ability of DG units to minimizing the network losses.
机译:将分布式发电(DG)引入分销网络对损耗具有显着影响。根据DG单位分配的位置和它们具有尺寸的位置,这种效果可能是有害的或有益的。本文涉及DG单位的最佳选址和尺寸,以使双向和单向电流场景下的径向分配网络中的总功率损耗最小化。增强的遗传算法(EGA)用于有效地探索问题搜索空间。此外,还提供了简单且直接的惩罚功能,其中不需要违规的归一化。该方法在典型的16总线分配网络上实现和测试。仿真结果表明,单向流量约束可能限制DG单元以最小化网络损耗的能力。