Islanding detection and protection is an important concern for grid connected photovoltaic (PV) power generation system due to personnel and equipment safety. Over/under voltage protection (OVP/UVP) and over/under frequency protection (OFP/UFP) are basical inverter resident passive islanding detection method (IDM) for detecting an islanding condition by monitor parameters in point of common coupling (PCC) such as voltage amplitude and frequency and then cause the inverter to shut down when there is sufficient transition from normal specified conditions. The real and reactive power equations and Non-Detection Zone (NDZ) of OVP/UVP and OFP/UFP methods for grid connected PV system are derived and analyzed in this paper. Analyses show that the behavior of the system at the time of disconnection will depend on the imbalance power at the instant before the switch opens to form the island, these results also indicate the NDZ of OVP/UVP and OFP/UFP methods is considerable large and the reaction times for these protective methodologies may be variable or unpredictable.
机译:孤岛检测和保护是电网连接的光伏(PV)发电系统由于人员和设备安全的重要问题。过/欠电压保护(OVP / UVP)和上/下频率保护(OFP / UFP)是用于在公共耦合点(PCC),例如检测由显示器参数孤岛条件basical逆变器驻留被动孤岛检测方法(IDM)电压的幅值和频率,然后导致变频器关闭时存在来自正常指定的条件足够的过渡。有功和无功功率方程和非检测区间OVP / UVP的(NDZ)和OFP / UFP方法电网连接的PV系统导出并在本文中进行分析。分析表明,该系统在断开时的行为将取决于不平衡功率的瞬间,开关打开,形成岛之前,这些结果还表明OVP / UVP和OFP的NDZ / UFP方法是相当大,对于这些保护方法的反应时间可以是可变的或不可预测的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号