EXPERIMENTAL INVESTIGATION OF OPERATING CHARACTERISTICS AND ENERGY CONSUMPTIONS FOR A VERTICAL FREEZER VARYING THE REFRIGERANT CHARGE

机译:改变制冷剂充电的垂直冷冻机的操作特性和能量消耗的实验研究

获取原文

摘要

During steady-state working conditions, in small capacity mechanical vapour-compression refrigerating systems using capillary tubes and without refrigerant accumulators, refrigerant charge affects the values of the main operating parameters. In order to establish the influence of refrigerant charge distribution on working conditions, the results of an experimental investigation for a vertical freezer of 320 dm3 with diabatic capillary tube are reported, varying the charge of isobutane between 55 g and 200 g at constant ambient temperature. The results showed that, increasing the charge, the subcooling degree at condenser exit, the evaporating and the condensing pressures, the mass flow rate increase, while superheating degree at evaporator exit decreases. An optimum charge with respect to energy consumption was found.
机译:在稳态工作条件下,在小容量的机械蒸汽压缩制冷系统中使用毛细管和没有制冷剂蓄能器,制冷剂电荷影响主要操作参数的值。为了建立制冷剂电荷分布对工作条件的影响,报道了用糖尿病毛细管的320dM3的垂直冷冻箱的实验研究结果,在恒定的环境温度下改变了55克和200g的异丁烷的电荷。结果表明,增加电荷,冷凝器出口的过冷度,蒸发和冷凝压力,质量流量增加,而蒸发器出口的过热程度降低。发现了关于能量消耗的最佳电荷。