It is known that many failures of power transformers are related to aging effects of the on-load tap changer contacts. This paper discusses the recently developed analysis method for service aged power transformers. In particular, the effect of several aging stages of the tap changer change-over selector contacts on dynamic resistance have been considered. As a result, to assess on-site the condition of a power transformer, the following approaches are combined: (1) The dynamic resistance measurement, to detect deviant contact resistances inside an on-load tap changer; (2) The velocity measurement to the driving axis of the tap changer drive mechanism and the motor power measurement on the drive motor of the tap changer, to detect mechanical wear or damage inside the drive mechanism; (3) Transformer turns ratio measurement and DC winding resistance measurement, to diagnose the transformer windings. This paper also presents decision support rules for dynamic resistance measurements to make an unambiguous decision about the status of the tap changer contacts.
机译:众所周知,功率变压器的许多故障与载荷分接换动器触点的老化效果有关。本文讨论了最近开发的用于服务老化电力变压器的分析方法。特别地,已经考虑了多次变换器改变选择器触点对动态电阻的几个老化阶段的效果。结果,为了评估现场电力变压器的条件,以下方法组合:(1)动态电阻测量,检测载荷龙头换动器内的偏差接触电阻; (2)分接开关机构的驱动轴的速度测量和分接开关的驱动电机上的电机功率测量,检测驱动机构内的机械磨损或损坏; (3)变压器转动比率测量和直流绕组电阻测量,诊断变压器绕组。本文还展示了动态电阻测量的决策支持规则,以便明确决定分接开关联系人的状态。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号