Optimum detector bandwidth selection for partial discharge testing of high voltage power cables is discussed in this paper. The analysis is based on analytical models already described in literature, whose parameters have been validated by lab tests. The results indicate that when testing cables system on an accessory-per-accessory basis a detection bandwidth of few tens of MHz ensures: (a) large sensitivity to PD that could originate in the accessories as well as in the cable, (b) the capability of separating pulses coming from different parts of the power system and, thus, providing an approximate location of PD sources.
机译:本文讨论了高压电力电缆的局部放电测试的最佳检测器带宽选择。分析基于文献中已经描述的分析模型,其参数已通过实验室测试验证。结果表明,当对电缆系统以附件的基础上测试电缆系统时,少数MHz的检测带宽可确保:(a)对PD的较大敏感性,可以源于附件以及电缆(B)从电力系统的不同部分分离脉冲的能力,从而提供PD源的近似位置。