首页> 外文会议>Conference Record of the IEEE International Symposium on Electricity Insulation >Temperature and load correlated on-line PD measurements on a Danish 6,4MVA Power Generator
【24h】

Temperature and load correlated on-line PD measurements on a Danish 6,4MVA Power Generator

机译:丹麦6,4mVA发电机上的温度和负载相关在线PD测量

获取原文

摘要

Monitoring of the PD level of a 10kV, 6,4MVA generator in a Danish Power Plant over a couple of years has caused increasing concern about the generator's VPI insulation condition. This paper presents an analysis of the PD activity in the generator with an advanced PD monitoring system. The measurements were performed as on-line measurements during normal operation as well as during the start up and shut down sequences. Winding temperature and the generator load were recorded simultaneously with the PD measurements. A correlation has been established between the temporal development of PD intensity and factors like winding temperature and load level. Analyses were performed on the PD development with respect to pulse magnitude and frequency, including advanced pulse shape analyses, in order to determine PD-origin and characteristics. A comparable high PD level was recorded which, combined with experiences from early types of generators with global VPI insulation, led to the decision that the generator should be refurbished. The results described and analyzed in this paper are based on the service period with the original insulation until refurbishment.
机译:在几年内丹麦电厂中监测10kV,6,4mVA发电机的PD水平,对发电机的VPI绝缘条件造成了越来越多的关注。本文提出了具有高级PD监控系统的发电机中PD活动的分析。在正常操作期间以及在启动和关闭序列期间,在线测量进行测量。绕组温度和发电机负载与PD测量同时记录。在Pd强度和绕组温度和载荷水平等因素的时间开发之间建立了相关性。关于脉冲幅度和频率对PD开发进行分析,包括高级脉冲形状分析,以确定PD-原点和特性。记录了可比的高PD级别,与全球VPI绝缘的早期发电机的经验相结合,导致了发电机应该翻新的决定。本文描述和分析的结果基于具有原始绝缘的服务期,直到翻新。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号