首页> 外文会议>International Conference on High Voltage Engineering and Application >Effects on Transformer due to UHVDC Mono-polar Operation and Calculation of Ground Electrode Current
【24h】

Effects on Transformer due to UHVDC Mono-polar Operation and Calculation of Ground Electrode Current

机译:由UHVDC单极的操作和接地电流计算的变压器对变压器的影响

获取原文

摘要

Recently years, UHVDC transmission system is paid more attention to in the field of China's power system. It takes key part in the tactic of China electrical power development. But, many problems caused by UHVDC system, such as DC bias, corrosion of metal underground and so on. DC flows through the neutral point and causes DC bias of transformer, as well as some other problems, such as vibrations, overheating, or noise, which will harm the operation of transformer. In this paper, the influences of DC grounding current on transformer, caused by UHVDC Mono-polar operation, are introduced. And, some suggestions of DC bias solution were provided.
机译:近年来,UHVDC传输系统在中国电力系统领域得到了更多关注。它采用了中国电力发展策略的关键部分。但是,UHVDC系统造成的许多问题,如DC偏置,金属地下腐蚀等。 DC流过中性点并导致变压器的直流偏置,以及其他一些问题,如振动,过热或噪音,这将损害变压器的操作。本文介绍了由UHVDC单极运算引起的DC接地电流对变压器的影响。并且,提供了DC偏压解决方案的一些建议。