首页> 外文会议>IEEE International Conference on Signal Processing and Communications >SIGNAL PROCESSING APPLICATIONS TO CURRENT TRAVELING WAVE FAULT LOCATORS FOR EHV TRANSMISSION NETWORKS
【24h】

SIGNAL PROCESSING APPLICATIONS TO CURRENT TRAVELING WAVE FAULT LOCATORS FOR EHV TRANSMISSION NETWORKS

机译:信号处理应用于EHV传输网络的当前行波故障定位器

获取原文

摘要

Traveling Waves Recorders (TWRs) are used to accurately find the location of different faults in power transmission networks. These recorders are installed at few high voltage buses where current traveling waves (CTWs) can be extracted. The CTW signals' time delay of the initial wave is recoded at each TWR. In this paper, the minimum travel time of the CTW has been calculated considering Dijkstra algorithm to select the nearest TWRs to the fault point. Wavelet Transform is used to find the highest energy of the details frequency band of the CTW signals. Optimum details level is extracted based on its energy content. The mean delay is calculated from the first packet of details' power profile for each TWR to be used in a double-end fault location algorithm. Time delay at the maximum power delay profile shows good results compared to the mean time delay.
机译:旅行波录像机(TWRS)用于准确找到电力传输网络中不同故障的位置。这些记录器安装在很少的高压总线上,可以提取电流行驶波(CTW)。在每个TWR上重新编码初始波的CTW信号的时间延迟。在本文中,考虑到Dijkstra算法来计算CTW的最小行程时间,以选择最接近的TWR到故障点。小波变换用于找到CTW信号的细节频带的最高能量。基于其能量内容提取最佳细节级别。根据每个TWR的细节的第一分组计算平均延迟,以用于双端故障定位算法。与平均时间延迟相比,最大功率延迟配置文件的时间延迟显示出良好的结果。