INCORRECT USE OF FUSE CHARACTERISTICS IN IEC 62271-105 RESTRICTS H.V. FUSE APPLICATION IN RING MAIN UNITS

机译:在IEC 62271-105中使用熔丝特性的使用不正确限制H.V.环形主机中的保险丝应用

获取原文

摘要

IEC 62271-105 "Alternating current switch-fuse combinations" goes back to IEC 420:1973, when relatively slow acting switches in air and under oil were used in ring main units. SF{sub}6 insulated switchgear did not exist in m.v. secondary distribution systems by than. This may explain why no one cared about the limitations in the use of fuse time-current characteristics in a time range below 100 ms. The paper highlights the conflicting claims of IEC. 62271-105 to IEC 60282-1 "High voltage fuses" and IEC TR 60787 "Application guide for the selection of high voltage current-limiting fuse-links for transformer circuits" and explains the consequences with respect to h.v. fuse application in combinations with SF{sub}6 switches. Indeed, important and well established fuse applications will virtually be ruled out by IEC 62271-105. Alternative proposals are presented to resolve the conflicting situation in the International Standards.
机译:IEC 62271-105“交替电流开关 - 保险丝组合”返回到IEC 420:1973,当空气中的相对慢的作用开关和油下方的环主机时。 SF {Sub} 6绝缘开关设备在M.V中不存在。二级分配系统比。这可以解释为什么没有人在100ms低于100毫秒的时间范围内使用熔丝时间电流特性的限制。本文突出了IEC的冲突偏差。 62271-105至IEC 60282-1“高压保险丝”和IEC TR 60787“选择用于变压器电路的高压电流限制保险丝连杆的应用指南”并解释了对H.V的后果。用SF {Sub} 6交换机组合熔断器应用。实际上,ICEC 62271-105实际上将排除重要且成熟的保险丝应用。提出了替代方案,以解决国际标准中的矛盾情况。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号