首页> 外文会议>International Workshop on Energy and Environment of Residential Building >Measurement and analysis of the application of heat recovery ventilator in a residential room in cold region of China
【24h】

Measurement and analysis of the application of heat recovery ventilator in a residential room in cold region of China

机译:热回收呼吸机在中国寒冷地区住宅室中的应用分析

获取原文

摘要

Recently years, the insulation and airtightness of building envelope are strengthened greatly due to the demand of energy conserving. As a result, insufficient ventilation leads to a worse Indoor Air Quality (IAQ), especially in heating seasons in the cold region of China. This paper describes the results of measurements of Heat Recovery Ventilator (HRV) in Harbin (China) in winter. Temperature, humidity, and CO2 were measured to assess performance of HRV. The measurements were taken over a three - to four - day period in a residential room with normal occupancy. The average CO2 concentration was 788 ppm while the HRV was in operation, which meets the requirements of Indoor Air Quality of China ( GB/T 18883 - 2002 ). The thermal environment didn't be much affected during the HRV being turned on. There was a 1.8 °C indoor average temperature drop due to the switch on of the HRV. An overall average temperature efficiency was 82.6% during the test period of HRV being turned on. Therefore, HRV is an effective instrument to improve IAQ in cold region of China in heating seasons. Further study should be made for the application of HRV in cold region of China.
机译:近年来,由于节能的需求,建筑信封的绝缘和气密性得到了大大加强。结果,通风不足导致更糟糕的室内空气质量(IAQ),特别是在中国寒冷地区的加热季节。本文介绍了冬季哈尔滨(中国)热回收呼吸机(HRV)测量结果。测量温度,湿度和CO 2以评估HRV的性能。测量在一个常规占用的住宅室中的三到四天拍摄。平均二氧化碳浓度为788ppm,而HRV在运行中,符合中国室内空气质量的要求(GB / T 18883 - 2002)。在接通时,热环境并没有受到很大的影响。由于HRV开关,有1.8°C的室内平均温度降。在接通的HRV的测试期间,总平均温度效率为82.6%。因此,HRV是在加热季节中改善中国寒冷地区IAQ的有效仪器。还应进一步研究HRV在中国寒冷地区的应用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号