首页> 外文会议>Natural Gas Technologies Annual Conference and Exhibition >Analysis of Optimizing Running Way of Water Chillers
【24h】

Analysis of Optimizing Running Way of Water Chillers

机译:水冷却器优化运行方式分析

获取原文

摘要

The operation of refrigerating systems using screw water chillers is optimized from the point of energy consumption. Optimization is made on the basis of annual air conditioning dynamic load and the performance of screw water chillers under partial load. The result of calculation shows that even if air-conditioning load is lower than the rated capacity of two chillers, there still is the possibility that the energy consumption of three chillers is lower than that of two chillers. Energy saving calculated in this paper can reach 10 % by optimizing running way of water chillers. The conclusion is: from the viewpoint of energy saving, operation of screw water chillers should be optimized to reach the highest energy efficiency, but not under the 100 % rated capacity as usual.
机译:使用螺杆水冷却器的制冷系统的操作从能量消耗进行了优化。优化是在年度空调动态负荷和螺杆水冷钻的基础上进行的局部载荷进行。计算结果表明,即使空调负荷低于两个冷却器的额定容量,仍然有可能的三个冷却器的能量消耗低于两个冷却器的能耗。通过优化水冷钻的运行方式,本文计算的节能可达到10%。结论是:从节能的观点来看,应优化螺杆水冷钻的操作,以达到最高能量效率,但不受惯常的100%额定容量。