首页> 外文会议>International Conference on Power Systems Technology >The Calculation of HV Capacitor Unbalance Protection Settings for AC Filters in GeZhouBa Converter Station
【24h】

The Calculation of HV Capacitor Unbalance Protection Settings for AC Filters in GeZhouBa Converter Station

机译:葛洲坝换算站交流滤波器HV电容不平衡保护设置的计算

获取原文

摘要

AC filters are important harmonics filtering equipment in HVDC transmission. The high voltage capacitor failure in AC filters is incidental. Some elements failure cannot be detected by the traditional protection due to the small fault current. The capacitor unbalance protection is designed for this situation to protect the high voltage capacitor units in the H-bridge against avalanche effects and avoid AC Filter life reduction. In this paper, the principle of the capacitor unbalance protection and the unbalance current calculation are introduced in detailed. Both tool and model used for unbalance current calculation are described. The unbalance current in different cases is calculated for AC filters in GeZhouBa converter station. Three levels of capacitor element failure detection are provided: one for alarm, one for delayed trip and one for immediate trip. Some conclusions are made for the protection configuration and principles applied in the later project.
机译:交流滤波器是HVDC传输中的重要谐波过滤设备。交流滤波器的高压电容器故障偶然。由于小故障电流,传统保护无法检测到一些元素故障。电容器不平衡保护专为这种情况而设计,以保护H-Bridge中的高压电容器单元免受雪崩效果,并避免AC滤波器寿命。在本文中,详细介绍了电容器不平衡保护的原理和不平衡电流计算。描述了用于不平衡电流计算的工具和模型。针对葛洲巴转换器站的交流滤波器计算不同情况下的不平衡电流。提供了三个电容器元件故障检测:一个用于报警,一个用于延迟行程,一个用于立即跳闸。一些结论是用于在后来项目中应用的保护配置和原则。