Field test results of an Italian 380 kV top-down Restoration strategy from neighboring power systems supplying very long restoration path

机译:来自邻近电力系统的意大利380 kV自上而下恢复策略的现场测试结果,提供了非常长的恢复路径

获取原文

摘要

The paper describes the preparation and execution of a Top-Down Restoration strategy using 380 kV backbone supplied from a bordering national power system recently carried out as basic part of the scheduled tests recommended in ENTSO-E Operation Handbook (Policy 5) as well as in future European Network Code on Emergency and Restoration, entered in force on December 2017. Top-Down Restoration test here presented has very exceptional features basically due to the very high length of High Voltage (HV) Overhead Transmission Lines (OTLs) involved, specifically more than 1400 km from South of France to South of Italy. Actually, some tricky issues can be detected that must be properly considered during the preparation and execution of the test. Some of the findings described in the present paper are also outcomes of the preceding tests using the same strategy, in similar or analogous paths, performed in the past years on the Italian transmission system: this last test was successful also thanks to the improvements implemented in several system components, in the simulation models and in the procedure itself.
机译:本文介绍了使用从边界国家电力系统提供的380 kV骨架的准备和执行,最近作为ento-e操作手册(政策5)建议的预定测试的基本部分,以及未来的欧洲网络守则在2017年12月进入的紧急和恢复。此处的自上而下的恢复测试基本上具有非常出色的功能,由于涉及的高电压(HV)架空传输线(OTL)的高度长度非常高,特别是更多距离法国南部仅1400公里到意大利南部。实际上,可以检测到一些棘手的问题,必须在准备和执行测试期间正确考虑。本文中描述的一些发现也是使用相同或类似的策略的前面测试的结果,在意大利传输系统的过去几年中进行的相同或类似的路径:由于所实施的改进,这次测试也取得了成功几个系统组件,在模拟模型和过程本身中。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号