Overheating of Grounding Wire Clamps of Transmission Lines - Diagnostics, EMTP Investigation and Solution Suggestion

机译:接地线夹具的过热 - 诊断,EMTP调查和解决方案建议

获取原文

摘要

Overheating of ground wires clamps was revealed during a helicopter thermovision inspection carried out in the years of 2014 and 2015. This problem appeared on three lines owned by the Czech Transmission System Operator. Measured temperature of some of the overheated ground wire clamps reached relatively high values (up to 400°C). Based on this finding, several affected clamps on the 400 kV line were dismounted and examined. Footprints of heat stress was found on it. Even partial melting and welding of cast-iron and steel parts occurred in several cases. This paper deals with possible root cause analysis of the overheating phenomena. Mathematical model of affected lines was created and induced currents were examined for various grounding wires connection schemes and clamps contact resistances. A solution of the problem is suggested.
机译:在2014年和2015年的直升机热敏检查期间揭示了地线夹具的过热。这个问题出现在捷克传输系统运营商拥有的三条线上。一些过热的接地线夹的测量温度达到相对高的值(最多400℃)。基于该发现,400 kV线上的几种受影响的夹具被拆除并检查。在它上发现了热应激的脚印。甚至在几种情况下也发生了铸铁和钢部件的部分熔化和焊接。本文涉及可能对过热现象的根本原因分析。采用受影响线的数学模型,针对各种接地线连接方案进行了诱导电流,并夹紧接触电阻。提出了问题的解决方案。