首页> 外文会议>CIGRE Session >Disconnectors reliability on the French grid and means to reduce the consequences of their failures on the electrical system
【24h】

Disconnectors reliability on the French grid and means to reduce the consequences of their failures on the electrical system

机译:隔离对法国网格的可靠性,并使其在电气系统上减少失败的后果

获取原文
获取外文期刊封面目录资料

摘要

The function of a disconnector is quite simple on a mechanical and electrotechnical level: to isolate or to connect part of a grid on various electrical nodes, to establish an electrical continuity and to allow the transfer of current between 2 isolated parts of a substation. This apparent simplicity has probably led to pay less attention to the reliability of this equipment by being satisfied, for example, with an indirect signaling of the position of its HV contacts, and the lack of information to apprehend if they are still able to fulfill their function over time. Indeed, the active part and the control cabinet of these devices are constantly subjected to external climatic conditions which generate, on one hand, more important aging phenomena than for other equipment, with 2/3 of the hotspots detected on the network, and on the other hand, makes its kinematics subject to mechanical seizures. However, any network operator knows that the consequences of a disconnector failure (bus bar fault, total loss of the substation) are very disproportionate with the anomaly causing this failure (loss of clamping in the linkage, erroneous information). After a summary of the behavior of the disconnectors on the French grid and the main consequences for the system operation, this article presents the ongoing developments, tested as demonstrators in some RTE substations to make these devices more reliable. These developments are based on communication and lean on: - Torque measurements in the control cabinet that detect either an early seizure in the kinematic and require intervention for maintenance or a break in kinematics by the detection of sub-torque. - Pressure and temperature measurements at the male and female contacts of the live parts in order to guarantee the closed position of the disconnector to the operator with a nominal transit capacity and to follow up this pressure and temperature evolution with time to detect any aging of the device. - The measurement of the actual position of the active parts when opening to guarantee the minimum isolation distance, especially when the disconnector is operated remotely. A presentation of the implementation of these different solutions and their benefits for a Transmission System Operator is carried out.
机译:在机械和电气技术等级上的函数非常简单:要在各种电节点上隔离或连接一部分电网,以建立电连续性,并允许在2个变电站的2个隔离部分之间传递电流。这种明显的简单性可能导致通过满足,例如,通过满足其HV接触的位置的间接信号传导,如果它们仍然能够满足他们的信息,则不能关注该设备的可靠性随着时间的推移。实际上,这些装置的活性部分和控制柜不断受到外部气候条件,在一方面,更重要的老化现象比其他设备更重要,在网络上检测到的热点中的2/3,以及另一只手,使其运动学受到机械癫痫发作。然而,任何网络运营商都知道断开的故障(母线故障,变电站总损失)的后果与导致此故障的异常非常不成比例(链接中夹紧的损失,错误的信息)。在Fring Conntors对法国网格的行为摘要之后,本文提出了正在进行的发展,作为一些RTE变电站的示威者测试,以使这些设备更加可靠。这些开发基于通信和倾斜: - 控制柜中的扭矩测量,检测运动中的早期癫痫发作,并通过检测子扭矩来要求维护或在运动学中的断裂。 - 动态部件的雄性和母触点处的压力和温度测量,以保证断开连接器的闭合位置,以标称传输容量,随时随地跟进这种压力和温度演变以检测任何老化设备。 - 打开以保证最小隔离距离时,有源部件的实际位置测量,特别是当远程操作断路器时。执行这些不同解决方案的实现及其对传输系统运营商的益处的介绍。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号