The permissible loading of transformers is determined by internal losses, radiated heat from sun exposure and radiation and convection heat losses. In countries with high temperatures and high solar radiation, the transformer rating can be increased by solar shield preventing the heating trough solar radiation. For 237 transformers (HV/MV) the influencing factors are discussed and analyzed and a cost comparison and economic evaluation was carried out. The results indicated, that solar shielding is applicable for transformers with rating above 18MVA, as the cost for the shields will be lower than the cost benefit for the expected transformer life time of 20 years.
机译:变压器的允许装载由内部损耗,辐射热来自阳光照射和辐射和对流热损失决定。在高温和高太阳辐射的国家,太阳能屏蔽可以增加变压器额定值,防止加热槽太阳辐射。对于237个变压器(HV / MV),讨论并分析了影响因素,并进行了成本比较和经济评估。所示结果,太阳能屏蔽适用于具有高于18MVA高于18MVA的变压器,因为屏蔽的成本将低于预期变压器寿命20年的成本效益。