首页> 外文会议>International Conference on Electric Utility Deregulation and Restructuring and Power Technologies >Online monitoring of winding deformation and error analysis based on transformer impedence circle character
【24h】

Online monitoring of winding deformation and error analysis based on transformer impedence circle character

机译:基于变压器阻抗圆形字符的绕组变形及误差分析在线监测

获取原文

摘要

This paper introduced the main point of three winding transformer impedance circle characters that is constructing the 3D locus between the voltage differences in the high- and low-(or middle-) sides of a particular phase against the cur rents of this two windings. In additional, error terms caused by exciting current of both two winding and three-winding trans former have been analyzed. Current compensation was employed to reduce error. A Matlab code was developed to calculate the feature parameter of the impedance circle character. Winding deformation can be diagnosed by comparing the index with the fingerprint. PSCAD simulation and fault recorder analysis results show that the technique is free from load, does not call for any special equipment and enable on-line monitoring.
机译:本文介绍了三个绕组变压器阻抗圆形字符的主要观点,该字符在特定阶段的高(或中间)侧面的电压差之间的3D基因座与该两个绕组的CUR租金之间的电压差。在额外的情况下,已经分析了由两个绕组和三绕组转换器的激励电流引起的误差术语。使用当前的补偿来减少误差。开发了MATLAB代码以计算阻抗圆字符的特征参数。可以通过将索引与指纹进行比较来诊断绕组变形。 PSCAD仿真和故障记录仪分析结果表明,该技术没有负载,不呼叫任何特殊设备并在线监控。