Static Synchronous Compensator (StatCom) has been proved to have a number of advantages over other techniques available at present in stabilizing power transmission system. To improve the stability of power transmission system of Henan province. Henan Electric Power Company and Tsinghua University have jointly investigated and developed a 20MVA StatCom employing GTO inverters. The StatCom consists of four six-pulse voltage source inverters (VSIs) unit rated 5MVA which use 48 GTOs rated 4500V, 4000A. The StatCom has been installed in a 220KV substation and has been put into operation successfully since April 1999. The field tests have been carried out to verify the performance and the long-term reliability of the installation. The outline, technical features and field test results of the 20MVA StatCom are given in this paper.
机译:已经证明静态同步补偿器(Statcom)已经以稳定电力传输系统目前的其他技术具有许多优点。提高河南省电力传输系统的稳定性。河南电力公司和清华大学共同调查,开发了一个20MVA attomcom,采用GTO逆变器。 Statcom由四个六脉冲电压源逆变器(VSIS)单元额定电压为5MVA,其中使用48 GTOS 4500V,4000A。 STATCOM已安装在220kV变电站中,并自1999年4月以来已成功投入运营。已经进行了现场测试以验证安装的性能和长期可靠性。本文给出了20MVA Statcom的轮廓,技术特征和现场测试结果。