首页> 外文会议>International conference on electrical engineering >LIGHTNING OVERVOLTAGE ANALYSIS OF KEPCO 765 kV GAS INSULATED SUBSTATION
【24h】

LIGHTNING OVERVOLTAGE ANALYSIS OF KEPCO 765 kV GAS INSULATED SUBSTATION

机译:KEPCO 765 KV气体绝缘变电站雷电过电压分析

获取原文

摘要

This paper describes the results of lightning overvoltage analysis and determination of BIL(Basic Lightning Impulse Insulation Level) of KEPCO 765kV gas insulated equipment by EMTPfElectro-Magnetic Transient Program). To get the reliable results, four section tower model is used and the voltage-time characteristics of the arcing horn gap is simulated by T ACS (Transient Analysis Control System) in EMTP. By the analysis results we determined the BIL of 2250 kV for the gas insulated buses and circuit breakers and 2050 kV for the transformer.
机译:本文介绍了EMTPCo电磁瞬态瞬态程序的Kepco 765kV气体绝缘设备的雷电过电压分析和雷达(基本雷电脉冲绝缘电平)的结果。为了获得可靠的结果,使用四个部分塔模型,并通过EMTP中的T ACS(瞬态分析控制系统)模拟电弧喇叭间隙的电压时特性。通过分析结果,我们确定了瓦斯绝缘总线和断路器的2250 kV的BIL,为变压器为2050kV。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号