首页> 外文会议>International conference on electrical engineering;ICEE'96 >LIGHTNING OVERVOLTAGE ANALYSIS OF KEPCO 765 kV GAS INSULATED SUBSTATION
【24h】

LIGHTNING OVERVOLTAGE ANALYSIS OF KEPCO 765 kV GAS INSULATED SUBSTATION

机译:KEPCO 765 kV气体绝缘变电站雷电过电压分析

获取原文

摘要

This paper describes the results of lightning overvoltage analysis and determination of BIL(Basic Lightning Impulse Insulation Level) of KEPCO 765kV gas insulated equipment by EMTPfElectro-Magnetic Transient Program). To get the reliable results, four section tower model is used and the voltage-time characteristics of the arcing horn gap is simulated by T ACS (Transient Analysis Control System) in EMTP. By the analysis results we determined the BIL of 2250 kV for the gas insulated buses and circuit breakers and 2050 kV for the transformer.
机译:本文介绍了雷电过电压分析的结果,并通过EMTPf电磁暂态程序确定了KEPCO 765kV气体绝缘设备的BIL(基本雷电脉冲绝缘水平)。为了获得可靠的结果,使用了四段塔模型,并通过EMTP中的T ACS(瞬态分析控制系统)模拟了电弧喇叭间隙的电压-时间特性。根据分析结果,我们确定气体绝缘母线和断路器的BIL为2250 kV,变压器的BIL为2050 kV。