首页> 外文会议>International Conference on Partial Discharge >A new PD calibration technique based on the transfer function of stator windings
【24h】

A new PD calibration technique based on the transfer function of stator windings

机译:一种基于定子绕组传递函数的新型PD校准技术

获取原文

摘要

Partial discharge (PD) calibration for PD detection in electrical machines must be done to obtain accurate and reliable measurement results. However, difficulties in PD calibration exist in that results from different machines cannot be compared on the basis of PD readings and different detectors applied to the same winding will generally produce different values of PD magnitude. This is due to the fact that the propagation of the discharge pulse from the discharge site to the detector is extremely complex owing to a series of factors, including attenuation, reflection, resonance, radiation, impedance mismatch, grounding, etc., which affect the PD test results. This problem is compounded by the variety of detectors in use with variable bandwidth, centre frequency, cut-off frequencies, amplification coefficients and input impedance.
机译:必须进行局部放电(PD)电机PD检测的校准,以获得准确可靠的测量结果。然而,在PD校准中的困难存在于不能在PD读数的基础上比较来自不同机器的结果,并且施加到相同绕组的不同检测器通常会产生不同的Pd幅度值。这是由于由于一系列因素,从排放部位传播来自排放部位到检测器的放电脉冲的传播非常复杂,包括影响的衰减,反射,谐振,辐射,阻抗失配,接地等PD测试结果。使用可变带宽,中心频率,截止频率,放大系数和输入阻抗的各种检测器复合了该问题。