首页> 外文会议>ASME/IEEE Joint Railroad Conference >Design of grounding systems for tri-met Portland westside light rail traction power substations
【24h】

Design of grounding systems for tri-met Portland westside light rail traction power substations

机译:Tri-Met Bortland Westside轻轨牵引力变电站接地系统设计

获取原文

摘要

The Westside and Hillsboro Light Rail extensions in Portland, Oregon were open for revenue service in September, 1998. The 18-mile extensions extend the existing Eastside line rail service from downtown Portland to downtown Hillsboro. Thealignment includes at-grade street crossings, street-running operation, several fully grade separated sections and a 3-mile tunnel.Primary power is provided by the utilities at 12.5 kV and rectified by 18 mainline traction power substations to deliver 750 dc power to the light rail vehicles. Each substation has three separate grounding systems: a) an ac ground mat designed per IEEEStd 80-1986 for safe step and touch potentials, b) a dc ground mat for dc surge arrestor ground; the dc switchgear enclosure is connected to the dc ground mat through a low-resistance grounding scheme, c) an isolated ground rod for the utility incomingshields.This paper provides a detailed technical description including grounding calculations for each grounding system. Test and measurement data obtained for the installed grounding systems are presented and discussed.
机译:俄勒冈州波特兰的西侧和希尔斯伯勒轻轨扩展在1998年9月,俄勒冈州的营业服务开放。18英里延伸将现有的东侧线路铁路服务从波特兰市中心到市中心的Hillsboro扩展。 Thealignment包括在级街道交叉口,街道运行运行,几个完全分离的部分和3英里的隧道。通过12.5 kV提供的公用事业提供了18个主线牵引力变电站,以向750直流电源进行整流轻轨车辆。每个变电站都有三个单独的接地系统:a)一个AC接地垫,设计为IEEESTD 80-1986,用于安全步骤和触摸电位,b)DC浪涌避雷器地面的直流接地垫; DC开关设备外壳通过低电阻接地方案,C)连接到DC接地垫,C)用于公用事业的接地杆。本文提供了详细的技术描述,包括每个接地系统的接地计算。提出并讨论了用于安装接地系统的测试和测量数据。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号