This paper presents a new practical backup power supply connection scheme for Distribution Line Non-Communication Protection (DNCP). Simulation tests have been conducted using the Alternate Transient Program (ATP) with respect to a typical single circuit breaker multi-section system. The results prove that the new scheme is able to not only recover the power supply of loads on healthy lines automatically, but also create disturbances in favor of Accelerated Over Current (AOC) criterion. Aiming at the failure of Directional Under Voltage (DUV) criterion derived from high voltage and large capacity induction motor load, a novel criterion using the increment of reactive power is proposed.
机译:本文提出了一种新的实用备用电源连接方案,用于配送线路非通信保护(DNCP)。已经使用相对于典型的单轮断路器多部分系统使用备用瞬态程序(ATP)进行仿真测试。结果证明,新方案不仅能够自动恢复健康线上的负荷电源,还可以创造有利于加速通过电流(AOC)标准的障碍。旨在在高电压和大容量感应电动机负载导出的电压(DUV)标准下的定向失效,提出了一种使用无功功率增量的新标准。