A New Voltage Sensorless Control Method for a Shunt Active Power Filter for Unbalanced Conditions

机译:一种用于不平衡条件的分流有源电力滤波器的新型电压无传感器控制方法

获取原文

摘要

Shunt active power filters (APFs) are utilized to correct power quality problems such as harmonic distortion and power system unbalance. Many control schemes for shunt APFs require measurement of both voltages and currents for the calculation of the instantaneous real and reactive power signals. The reference currents for the inverter in the APF are determined from these signals. Proposed in this paper is a voltage sensorless control method for a shunt APF which requires that only currents be measured. The reference currents for the inverter in the shunt APF are determined from the negative sequence components of these measured currents. Simulation and experimental results validate the performance of this control method even in the presence of unbalanced conditions.
机译:分流有源电力滤波器(APFS)用于校正电能质量问题,如谐波失真和电力系统不平衡。用于分流APF的许多控制方案需要测量用于计算瞬时实际和无功信号的电压和电流。 APF中的逆变器的参考电流由这些信号确定。本文提出的是一种用于分流APF的电压无传感器控制方法,其要求仅测量电流。分流APF中的逆变器的参考电流由这些测量电流的负序列分量确定。仿真和实验结果即使在存在不平衡条件下也验证了这种控制方法的性能。