This paper describes the behaviour of photovoltaic power plant inverter firmware on flicker level and reactive power at Point of Common Coupling in low voltage distribution system. During routine measurement of PQ the photovoltaic power plant was suspicious as a source of flicker in the distribution system. During PQ measurement using the common PQ analyser the distribution system operator could not identified the reason of high flicker. Using a tailored power quality analyser authors identified pulsed active power delivery during low sun radiation. Much smooth active power delivery was identified after the firmware upgrade.
机译:本文介绍了低压分布系统共同耦合点闪烁水平和无功功率对光伏电厂逆变器固件的行为。在PQ的常规测量期间,光伏发电厂作为分配系统中的闪烁源。在使用公共P​​Q分析仪的PQ测量期间,分配系统运营商无法确定高闪烁的原因。使用量身定制的电力质量分析仪作者在低阳光辐射期间确定了脉冲有源电力输送。固件升级后识别出很大的光滑的有效电力传递。