ENERGY SAVING ANALYSIS OF THE CENTRAL AIR-CONDITIONING CHILLER SYSTEM FOR A SHOPPING CENTER

机译:购物中心中央空调冷却系统的节能分析

获取原文

摘要

This paper took a shopping center building in central Taiwan as study case, and used dynamic simulation software eQUEST as tool. A model was built based on the existing air-conditioning system of the building. The number of hosts was changed and provided with different chilled water systems to analyze the effect on the annual energy consumption of the building. For model building, there were two 750RT centrifugal chillers and a PS chilled water system. The system control mode was constant primary flow/constant secondary flow. The built model was used as the reference point of comparison. The simulation used three quantities of chillers, including one set of 1500RT, two sets of 750RT and three sets of 500RT, and four systems, including PS system constant primary flow/constant secondary flow, PS system constant primary flow/variable secondary flow, constant primary flow system and variable primary flow system. There were 12 configuration modes for comparison. The result showed that the combination of three 500RT chillers and variable primary flow system has the best energy-saving effect. The overall energy consumption of air-conditioning system can be reduced by 16.48%, the energy-saving effect is significant.
机译:本文在台湾中央建筑占据了一座购物中心,作为学习案例,并使用动态仿真软件作为工具。基于建筑物的现有空调系统建立了模型。宿主数量已更改,并提供不同的冷却水系统,以分析对建筑物的年度能耗的影响。对于模型建筑,有两种750RT离心式冷却器和PS冷却水系统。系统控制模式是恒定的主流量/恒定次流。内置模型用作参考比较点。该模拟使用了三种冷却器,包括一组1500RT,两组750RT和三组500RT,四个系统,包括PS系统恒流/恒定的二次流量,PS系统恒定主流量/变量二次流量,常数主要流量系统和可变主流系统。有12种配置模式进行比较。结果表明,三种500RT冷却器和可变主流系统的组合具有最佳节能效果。空调系统的整体能耗可以减少16.48%,节能效果显着。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号