首页> 外文会议>IIR International congress of refrigeration >DUCTLESS AIR-CONDITIONING SYSTEM USING A COANDA EFFECT AND A HORIZONTAL PANEL FOR HERB MEDICINE STORAGE IN YUBARI PROJECT
【24h】

DUCTLESS AIR-CONDITIONING SYSTEM USING A COANDA EFFECT AND A HORIZONTAL PANEL FOR HERB MEDICINE STORAGE IN YUBARI PROJECT

机译:无导管空调系统使用柯桑效应和尤巴里项目的药草药物储存水平板

获取原文

摘要

This factory was built as base of herb medicine product, process and storage in Yubari, Hokkaido. It has three cold storages where 20m width, 60m depth and 6m height for keeping herb medicine. The Air- Conditioning system for this cold storage was planned based on three concepts, Economical, Reliability and Regionality. In order to achieve the purpose of this Air-Conditioning system such as to eliminate redundant storage space, to keep the room temperature and humidity as less than 15 degree or 60%, and to reduce the running cost, Ductless Air-Conditioning System using Coanda Effect and horizontal panel has been provided. CFD analysis has been used to determine the detail of this system, the number and layout of inducted-draft fans, the length of the horizontal panel, during design stage. And it was verified by actual measurement after the completion of construction. Compared to this system and original one, around 60% of electrical capacity was reduced.
机译:该工厂建于草药产品,工艺和储存的北海道。它有三个冷库,其中20米宽,60米深度和6米高,用于保留药草药物。根据三个概念,经济,可靠性和征区计划计划这种冷库的空调系统。为了达到这种空调系统的目的,例如消除冗余存储空间,使室温和湿度保持小于15度或60%,并减少运行成本,使用柯达的无管空调系统提供了效果和水平面板。 CFD分析已被用于确定该系统的细节,电感牵引风扇的数量和布局,在设计阶段期间水平面板的长度。并通过建设完成后的实际测量来验证。与该系统相比,原始的一个,大约60%的电容减少了。