首页> 外文会议>IET International Conference on Developments in Power System Protection >Comparison of different methods to limit short circuit currents in DC traction networks
【24h】

Comparison of different methods to limit short circuit currents in DC traction networks

机译:不同方法对直流牵引网络中短路电流的比较

获取原文

摘要

In this paper, different methods to limit short circuit currents in DC traction networks are compared. Typically, DC traction networks are supplied by the AC grid by means of an uncontrolled diode bridge rectifier. In case of a low-impedance short circuit fault between catenary and rail, the fault current reaches a large value. For densely meshed networks the mechanical circuit breakers can become too slow. The methods studied are applying fault current limiters, faster interruption of fault currents and adding controlled rectifiers. The fault current limiters considered are a reactor and a superconducting fault current limiter (SFCL). For faster interruption of fault currents, a hybrid circuit breaker is investigated. Simulations show that the short circuit current can be limited considerably by installing limitation devices after the rectifiers, when the short circuit occurs close to a substation. Fast interruption of the fault or application of the SFCL results in the strongest reduction of the short circuit current.
机译:在本文中,比较了不同方法来限制直流牵引网络中的短路电流。通常,通过不受控制的二极管桥式整流器通过AC电网提供DC牵引网络。在绕线和轨道之间的低阻抗短路故障的情况下,故障电流达到大值。对于密集的网状网络,机械断路器变得太慢。研究的方法正在应用故障电流限制器,更快地中断故障电流并添加控制整流器。考虑的故障电流限制器是反应器和超导故障电流限制器(SFCL)。为了更快地中断故障电流,研究了混合断路器。模拟表明,当短路发生在接近变电站时,通过在整流器之后安装限制装置,可以显着地限制短路电流。 SFCL的故障或应用的快速中断导致短路电流的最强降低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号