首页> 外文会议>12th IET International Conference on Developments in Power System Protection >Comparison of different methods to limit short circuit currents in DC traction networks
【24h】

Comparison of different methods to limit short circuit currents in DC traction networks

机译:直流牵引网络中限制短路电流的不同方法的比较

获取原文
获取原文并翻译 | 示例

摘要

In this paper, different methods to limit short circuit currents in DC traction networks are compared. Typically, DC traction networks are supplied by the AC grid by means of an uncontrolled diode bridge rectifier. In case of a low-impedance short circuit fault between catenary and rail, the fault current reaches a large value. For densely meshed networks the mechanical circuit breakers can become too slow. The methods studied are applying fault current limiters, faster interruption of fault currents and adding controlled rectifiers. The fault current limiters considered are a reactor and a superconducting fault current limiter (SFCL). For faster interruption of fault currents, a hybrid circuit breaker is investigated. Simulations show that the short circuit current can be limited considerably by installing limitation devices after the rectifiers, when the short circuit occurs close to a substation. Fast interruption of the fault or application of the SFCL results in the strongest reduction of the short circuit current.
机译:在本文中,比较了限制直流牵引网络中短路电流的不同方法。通常,直流牵引网络由交流电网通过不受控制的二极管桥式整流器供电。在悬链线和轨道之间发生低阻抗短路故障的情况下,故障电流将达到较大的值。对于网状密集的网络,机械断路器可能会变得太慢。研究的方法是应用故障电流限制器,更快地中断故障电流并添加受控整流器。所考虑的故障电流限制器是电抗器和超导故障电流限制器(SFCL)。为了更快地中断故障电流,研究了一种混合断路器。仿真表明,当短路发生在变电站附近时,通过在整流器之后安装限制装置可以大大限制短路电流。故障的快速中断或SFCL的应用会最大程度地降低短路电流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号