首页> 外文会议>Annual ISA POWID symposium >Guidelines for Tuning Cascade Controllers in Power Plants
【24h】

Guidelines for Tuning Cascade Controllers in Power Plants

机译:调谐电厂中级联控制器的指南

获取原文
获取外文期刊封面目录资料

摘要

The use of cascade control in certain power plant applications, such as drum level to feedwater flow control, is widely accepted, while its use in other applications, such as desuperheater temperature to spraywater flow control, is seldom used. Power plant consultants and academics have indicated that cascade control systems are difficult to tune and keep stable. Furthermore, opinions differ widely about the minimum safe ratio of inner loop speed to outer loop speed and how this ratio affects the stability and disturbance rejection of cascade control systems. This paper explores the effect of tuning and process dynamics on the stability of cascaded control loops using examples from power plant boilers. It explains how process characteristics and tuning methods are interrelated and when stability issues can be expected. The paper then presents guidance on the use of certain tuning rules and the minimum ratio between the speed of response of the outer and inner loops.
机译:在某些发电厂应用中使用级联控制,例如鼓电平到给水流量控制,广泛被接受,而其在其他应用中的使用,例如Desuper Heather温度到喷雾水流控制,则很少使用。电厂顾问和学者表示,级联控制系统难以调整和保持稳定。此外,意见差异很大,内部环路速度与外环速度的最小安全比以及该比率如何影响级联控制系统的稳定性和干扰抑制。本文探讨了调谐和过程动力学对级联控制回路的稳定性的效果,使用电厂锅炉的实例。它说明了如何相互关联的过程特性和调整方法以及何时可以预期稳定性问题。然后本文提出了关于使用某些调谐规则的指导和外部环路的响应速度之间的最小比率。