Quality level assessment of sorption chillers installed in solar cooling plants

机译:太阳能冷却厂安装吸附冷却器的质量水平评估

获取原文

摘要

The use of reliable, representative and reproducible data for the assessment of the quality level of HVAC systems and components on seasonal basis is crucial especially in view of the obligation of energy labelling, which is due by September 2015, and of the market surveillance. An analysis on the current normative framework dedicated to sorption chiller has revealed that no exhaustive references for sorption technologies and applications exist. Therefore, two test procedures aimed at the mapping of performances of sorption chillers at full and part load have been developed. The procedures developed take into account also different machines operating modes (i.e. continuous and discontinuous). A first attempt of validation of the test procedures has been carried out and here presented.
机译:使用可靠的,代表性和可重复的数据,用于评估HVAC系统和季节性基础上的质量水平,特别是考虑到能源标签的义务,这是2015年9月和市场监督的义务。对吸附冷却器专用于吸附冷却器的当前规范框架的分析揭示了没有对吸附技术和应用的详尽引用。因此,已经开发出全部旨在充分和部分载荷映射吸附冷却器性能的两种测试程序。制定的程序也考虑到不同的机器操作模式(即连续和不连续)。已经进行了第一次验证测试程序的尝试已经进行,这里提出。