首页> 外文会议>International Conference on Solar Heating and Cooling for Buildings and Industry >Field test results from combined solar thermal and air-source heat pump systems with a special focus on defrosting
【24h】

Field test results from combined solar thermal and air-source heat pump systems with a special focus on defrosting

机译:用于组合太阳能热和空气源热泵系统的现场测试结果,专注于除霜

获取原文

摘要

Three different combined solar thermal and air-source heat pump systems for domestic hot water preparation and space heating in single- and multi-family houses in Germany have been monitored since the beginning of 2012. Through these field test investigations component as well as system performances could be characterized and it was possible to identify errors regarding installation and control of the multiple operation modes. A particular attention was paid to the energetic effort and drop in thermal efficiency due to frosting and defrosting of the heat pump's evaporator. Furthermore, some of the descriptive parameters in the defrosting process (e.g. amount of energy required, work cycle between two defrosting modes) have been put in relation to the prevalent outdoor conditions (temperature, relative humidity). From this analysis the effectiveness of the applied defrosting strategy could be estimated, i.e. to which extent defrosting operation was initiated at the ideal point of time to be needed.
机译:自2012年初被监测为德国单家和多家庭住宅的国内热水准备和空间加热的三种不同的太阳能热泵系统。通过这些现场测试调查组件以及系统性能可以表征,并且可以识别关于多个操作模式的安装和控制的错误。由于热泵的蒸发器的磨砂和除霜,因此,特别注意的是充满活力的努力并降低了热效率。此外,除霜过程中的一些描述性参数(例如,所需的能量,两个除霜模式之间的工作循环)已经与普遍的室外条件(温度,相对湿度)相关。从该分析可以估计所施加的除霜策略的有效性,即在理想的时间点开始除霜操作的程度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号