Standby generation systems in low-voltage and medium-voltage applications connect to the utility power system in a number of different ways. Typically, an automatic transfer switch is a part of most power system connections. Engineers can choose three-pole or four-pole transfer switches for the intertie point. The application's sensitivity to a power interruption during switching helps determine transfer switch selection. The transfer switch can be contactor or circuit-breaker based or it can be a bypass design. At medium voltage, special requirements must be considered. Ultimately, the correct arrangement must be chosen depending upon grounding locations and neutral bonding. Incorrect power system bonding and grounding can cause unwanted transients or hazardous multiple grounds (improper ground-fault protection) depending upon transfer-switch selection. Improper design can create unintentional current paths and defeat ground fault protection. A transfer switch must be chosen for robust operation and maintenance at the beginning of the design process.
机译:低压和中压应用中的备用生成系统以多种不同的方式连接到公用电机系统。通常,自动转换开关是大多数电力系统连接的一部分。工程师可以为Intertie Point选择三极或四极转移开关。应用程序在交换过程中对电源中断的敏感性有助于确定传输开关选择。转移开关可以是基于接触器或断路器,或者它可以是旁路设计。在中电压下,必须考虑特殊要求。最终,必须根据接地位置和中性键合来选择正确的布置。根据转印开关选择,电源系统粘接和接地不需要导致不需要的瞬态或危险的多个地(不正确的地面故障保护)。设计不当可以创建无意的当前路径并打败接地故障保护。必须在设计过程开始时选择转移开关以用于鲁棒操作和维护。