首页> 外文会议>Simposio Brasileiro de Eletroquimica e Eletroanalitica >Study of the Corrosion of Buried Steel Grids of Electrical Power Transmission Towers
【24h】

Study of the Corrosion of Buried Steel Grids of Electrical Power Transmission Towers

机译:电力传动塔埋钢网格腐蚀研究

获取原文

摘要

The corrosion of metal structures in large facilities such as AC power transmission lines results in economic losses due to the necessary replacement of these structures and the interruption of power supply. To evaluate soil corrosion of the buried part of the structure the corrosion rate of AISI1020 steel samples was determined by weight loss measurements as a function of the exposure time to the soil close to a power transmission tower. The same measurements were made with samples which were connected to the tower while buried in the soil. By comparison of the two measurement series the influence of the AC power signal on soil corrosion can be studied.
机译:由于这些结构的必要替代和电源中断,大型设施中的金属结构腐蚀导致经济损失导致经济损失。为了评估结构的掩埋部分的土壤腐蚀,通过重量损失测量作为近距离传输塔的土壤的函数确定AISI1020钢样品的腐蚀速率。用埋在土壤中连接到塔的样品进行相同的测量。通过比较两种测量系列,可以研究AC电源信号对土壤腐蚀的影响。