首页> 外文会议>Congres International du Froid de I'IIF >A COMPARISON BETWEEN LITHIUM BROMIDE - WATER AND IONIC LIQUID - WATER AS WORKING SOLUTION FOR ABSORPTION REFRIGERATION CYCLES
【24h】

A COMPARISON BETWEEN LITHIUM BROMIDE - WATER AND IONIC LIQUID - WATER AS WORKING SOLUTION FOR ABSORPTION REFRIGERATION CYCLES

机译:溴化锂 - 水和离子液 - 水作为吸收制冷循环工作溶液的比较

获取原文

摘要

Reliable Vapour-Liquid-Equilibria (VLE) measurements are required for the estimation of the performance of an absorption chiller. Thus the water partial pressure of a mixture of water and a room temperature ionic liquid (RTIL) was measured in two different ways: Via Fourier-Transform-Infrared (FT-IR) Spectroscopy in a dynamic cell and via Raman-Spectroscopy in a static cell. Additional mixture properties as viscosity and specific heat capacity were measured as a function of concentration. An absorption chiller designed for LiBr - water with a nominal cooling capacity of 10 kW was operated with a mixture of diethylmethylammonium methanesulfonate (DEMA MeSO_3) and water in order to demonstrate the performance of new working solutions with RTILs. Although the measured Coefficient of Performance (COP) is comparable to the one of lithium bromide (LiBr) - water, the higher viscosities of working solutions with RTILs cause an insufficient heat and mass transfer which leads to a low refrigeration output.
机译:估计吸收冷却器的性能需要可靠的蒸汽 - 液体平衡(VLE)测量。因此,以两种不同的方式测量水和室温离子液体(RTIL)的混合物的水部分压力:通过动态细胞中的傅里叶变换红外(FT-IR)光谱,并通过静态通过拉曼光谱细胞。作为浓度的函数测量额外的混合物性能作为粘度和比热容。用甲磺酸二甲基甲基磺酸铵(Dema Meso_3)和水的混合物操作为Libr - 水的吸收冷却器,其具有10kW的10kW的水,以证明具有RTILS的新工作溶液的性能。尽管测得的性能系数(COP)与溴化锂(LIBR) - 水之一相当,但是具有RTILS的工作溶液的较高粘度导致不足的热量和质量传递,导致低制冷输出。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号