首页> 外文会议>Congres International du Froid de I'IIF >PERFORMANCE OF DOUBLE EFFECT SOLUTION TRANSPORTATION ABSORPTION CYCLE TO UTILIZE CONDENSATION HEAT OF REFUSE POWER GENERATION
【24h】

PERFORMANCE OF DOUBLE EFFECT SOLUTION TRANSPORTATION ABSORPTION CYCLE TO UTILIZE CONDENSATION HEAT OF REFUSE POWER GENERATION

机译:双效溶液运输吸收周期的性能利用垃圾发电的冷凝热

获取原文

摘要

The authors proposed heat transportation system based on ammonia absorption refrigeration cycle named STA. The idea is to transport ammonia solutions instead of chilled water from heat source side to heat demand side. It can transport thermal energy at ambient temperature because the system converts thermal energy into concentration difference of the solutions. However, because the COP of the ammonia based STA is not high enough, combination of LiBr absorption cycle to enhance the performance was proposed so that the COP could be doubled. The objective of the paper is to investigate the performance of the double effect STA to supply cooling. It was also attempted to apply the double effect STA to refuse power generation to utilize condensation heat to drive STA. The total performance of power generation and cooling supply was discussed in terms of primary energy reduction.
机译:作者提出了基于氨吸收制冷循环的热输送系统名为STA。这个想法是将氨溶液输送而不是从热源侧的冷冻水,以热量需求侧。它可以在环境温度下运输热能,因为系统将热能转换为溶液的浓度差异。然而,因为氨基氨基的STA不足以足够高,所提出了LIMB吸收循环的组合来增强性能,使得警察可以加倍。本文的目的是研究双重效果STA供电冷却的性能。还试图应用双效应STA来拒绝发电,以利用冷凝热来驱动STA。在一次能量减少方面讨论了发电和冷却供应的总性能。