We developed a method for estimating effective flow areas not only in the external wall of a house but also in the internal walls between rooms using only one type of tracer gas. This method is based upon the following hypotheses: (1) the temperature and tracer-gas concentration in the room is homogenous, (2) the air in the room is in a windless state, (3) there is no error in the measurement of tracer-gas concentration. However, we know that in reality, these hypotheses are not entirely true. To check the effects of discrepancies between the hypotheses and actual conditions on the estimated results, we set up a miniature model experiment. As a result of this experiment, it was clarified that the present estimation method yields a reasonable estimate of the discharge coefficient even when there is a certain amount of discrepancies between the hypotheses and actual conditions.
机译:我们开发了一种估计有效流动区域,不仅在房屋的外墙中估计有效流动区域,而且在房间之间的内壁中使用一种类型的示踪气体。该方法基于以下假设:(1)房间中的温度和示踪气体浓度是均匀的,(2)房间中的空气处于无风状态,(3)测量中没有误差跟踪气体浓度。然而,我们知道,实际上,这些假设并不完全正确。要检查假设与实际条件之间的差异对估计结果的影响,我们建立了一个微型模型实验。作为该实验的结果,澄清了本发明的估计方法即使在假设和实际条件之间存在一定量的差异也产生了对放电系数的合理估计。