CASE STUDY OF TCE ATTENUATION FROM GROUNDWATER TO INDOOR AIR AND THE EFFECTS OF VENTILATION ON ENTRY ROUTES

机译:地下水与室内空气中TCE衰减的案例研究及通风对入境路线的影响

获取原文

摘要

An investigation of groundwater -to-indoor air vapor intrusion of trichloroethylene (TCE) was conducted at a commercial building to 1) identify vapor pathways; 2) measure TCE attenuation ; 3) evaluate whether building pressurization can reduce vapor intrusion; and, 4) evaluate seasonal effects on vapor intrusion. The investigation included a site assessment, both indoor and outdoor air sampling, and the modification of the existing heating, ventilation and air-conditioning system. The investigation found that preferential pathways, such as a floor crack, acted as conduits for vapor intrusion when the building was not properly ventilated. The investigation also found that air TCE concentrations were significantly atte nuated between ground surface and the breathing zone and proper building pressurization can effectively minimize vapor intrusion. Weather conditions at the site did not significantly affect the indoor air TCE concentrations.
机译:对地下水的调查 - 在商业建筑物中进行三氯乙烯(TCE)的室内空气蒸汽侵入1)鉴定蒸气途径; 2)测量TCE衰减; 3)评估建筑加压是否可以降低蒸汽侵入; 4)评估对蒸汽侵入的季节性影响。调查包括一个现场评估,室内和室外空气采样,以及对现有的加热,通风和空调系统的改变。调查发现,当建筑物不适当通风时,优惠途径(如地板裂缝)充当用于蒸汽侵入的导管。调查还发现,空气TCE浓度在地面和呼吸区之间有显着讨论,并且适当的建筑加压可以有效地减少蒸汽侵入。该网站的天气状况并没有显着影响室内空气TCE集中。