A PIV EXAMINATION ON THE PERFORMANCE OF ULTRASONIC HEAT METER RELATED TO INSTALLATION

机译:关于安装超声波热量表的性能的PIV检查

获取原文

摘要

An experimental investigation was carried out on the performance of an ultrasonic heat meter with interference of non-uniformity from the upstream installation of a ball valve, which it is partly opened. It was found that the existence of the ball valve may under-report the flow, especially when the flow rate is low. From the measured PIV results, it can be found that the velocity distribution is obviously non-uniform inside the meter, and the change is remarkable when the inlet is added with a ball valve. The time resolved PIV results also demonstrate that the flow field becomes unsteady when slow down the flow rate, which might be responsible for the measurement deviation.
机译:对超声波热量表的性能进行了实验研究,从滚珠阀的上游安装的干涉,其部分打开。结果发现,球阀的存在可能在报告流动下,特别是当流速低时。从测量的PIV结果,可以发现,仪表内部的速度分布显然是不均匀的,并且当入口加入球阀时,变化是显着的。解决时间解决的PIV结果还表明,在减慢流速时,流场变得不稳定,这可能负责测量偏差。