首页> 外文会议>International Conference on Indoor Air Quality and Climate >ESTIMATED VENTILATION RATES AND WORK-RELATED SYMPTOMS IN U.S. OFFICE BUILDINGS - THE BASE STUDY
【24h】

ESTIMATED VENTILATION RATES AND WORK-RELATED SYMPTOMS IN U.S. OFFICE BUILDINGS - THE BASE STUDY

机译:美国办公楼估计的通风率和与工作有关的症状 - 基础研究

获取原文

摘要

Insufficient information has been available on measured ventilation rates and symptoms in office workers. Using U.S. EPA data from 100 large U.S. office buildings, we assessed relationships in multivariate models between ventilation/person and lower respiratory and mucous membrane symptoms. Three preliminary ventilation estimates were used, based on CO2 ratio in airstreams, peak indoor CO2 concentrations, and volumetric estimates of flow rates. Ventilation rates (VRs) from 6-17 cfm/person above the current 20 cfm/person guideline for offices were associated generally with reduced symptom prevalence, but further benefits were not evident from higher YRs. For all ventilation estimates, higher occupant density was independently associated with more symptoms.Findings suggest that VRs somewhat above current guidelines would reduce symptoms in office workers, and that occupant density may play an unrecognized role in ventilation requirements. Different findings for the various ventilation estimates were surprising. Clarification of these relationships, and validation of VR measurement methods are necessary.
机译:在办公室工作人员中的测量通风率和症状都提供了足够的信息。使用来自100个大型美国办公楼的美国EPA数据,我们评估了通风/人和呼吸道和粘膜症状之间多变量模型中的关系。使用三种初步通风估计,基于SICSTREAS,峰值室内CO2浓度和流量率的体积估计。通风率(VRS)从6-17 CFM /人员上方的20个CFM /人员的办公室指南通常随着症状患病率降低而相关,但从较高的YRS中,进一步的益处并不明显。对于所有通风估计,较高的乘员密度与更多症状独立相关.Findings表明VRS略微上述目前的准则将减少办公室工作人员的症状,并且该乘员密度可能在通风要求中发挥无法识别的作用。各种通风估计的不同调查结果令人惊讶。阐明这些关系,并且需要VR测量方法的验证。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号