NUMERICAL AND EXPERIMENTAL STUDY OF THE AIR DISTRIBUTION IN A NEGATIVE PRESSURE ISOLATION WARD

机译:负压隔离区空气分布的数值和实验研究

获取原文

摘要

In healthcare facilities, the proportion of the healthcare professionals affected reached a surprising level during the SARS spreading period in China in 2003. The poor air distribution and ventilation strategy in the existed isolation wards contribute to bad indoor air quality situation. According to an actual negative pressure isolation ward in Beijing, which was used to isolate SARS patients, this paper carried out the numerical simulation and valid experiment to optimize the indoor air distribution for it. The result showed it is an acceptable ventilation system the supply air distributor is placed in one side of the ceiling opposite the patient's bed- head exhausts when the patient breathes peacefully. But the concentration of contaminant of the Breathing Zone of the Healthcare professionals would reach a high level when the patient is coughing severely although the decay of it would be fast.
机译:在医疗保健设施中,医疗保健专业人员的比例在2003年中国SARS传播期内达到了令人惊讶的水平。存在的隔离病房的空气分配和通风策略差有助于室内空气质量差。根据北京的实际负压隔离病房,该论文进行了分离SARS患者,进行了数值模拟和有效实验,以优化室内空气分配。结果表明,当患者平静地呼吸时,供应空气分配器放置在患者床头排气的天花板的一侧。但是当患者严重咳嗽时,医疗保健专业人员的呼吸区的污染物的浓度将达到高水平,尽管它的腐烂是快速的。