Kidd Creek mine in north western Ontario is developing phase 1 of the deep mine project for mining between 2100 m and 3100 m below surface. Heat problems were experienced during the 2003 summer in working places about 2300 m below surface. At the time the mine had a 'cold stope' for cooling the air supplied to the mine below 1500 m from surface. The 'cold stope' is where during winter, ice is created in both the open pit and its connecting airways to the mine and used to cool air in summer. The operation and limitations of the existing cold stope were evaluated and led to the requirement for additional mechanical cooling to be available for the summer of 2004. The first stage of a surface refrigeration plant providing 7.5 MWR of cooling was approved, the compressor set was ordered in early January 2004 and the plant commissioned six months later in early July 2004. Based on the current modifications to the mining plan, further plant expansions are required in 2006 and 2009 leading to a total of 19 MWR of mechanical refrigeration and 8.5 MWR equivalent from the extended cold stope. The refrigeration system is described with emphasis on the specific adaptations necessary to suit Canadian conditions. Additional investigations were; using the refrigeration compressors in winter for heating and, extending the performance of either cold stopes or alternative ice storage systems. The winter use of refrigeration involve removing heat from the mine exhaust air to provide a cooling load and to use the hot water in the condensing circuit to heat the intake air and reduce reliance on mine air heating with natural gas. This paper follows on from an earlier one presented at the Seventh International Mine Ventilation Congress where the background and planning of the mine ventilation and cooling requirements were described for extending the mine at depth to 3100 m.
机译:北西部的Kidd Creek Lime正在开发深入矿工的第1阶段,用于2100米和3100米以下。在2003年夏季在表面下方约2300米的工作场所举办了炎热问题。当时矿井有一个“冷空洞”,用于冷却供应到1500米的空气距离表面下方。 “冷身”是冬季的地方,冰是在露天坑和它的连接气道到矿山的,并用来夏天冷却空气。评估了现有的冷迹的操作和局限,并导致了2004年夏季可用的额外机械冷却的要求。批准了压缩机集提供了7.5MWR冷却的表面制冷设备的第一阶段。 2004年1月初和2004年7月初六个月后的工厂。根据目前对采矿计划的修改,2006年和2009年需要进一步的植物扩展,导致19 MWR的机械制冷和8.5 MWR等同物延长的寒冷。描述了制冷系统,重点是适合加拿大条件所需的具体适应。额外的调查是;在冬季使用制冷压缩机进行加热,并延长冷止挡或替代冰储存系统的性能。冬季使用制冷的涉及从矿井排出空气去除热量,以提供冷却负载和使用热水在冷凝电路以加热吸入空气,并减少对用天然气矿井空气加热的依赖。本文从第七届国际矿山通风大会上提出的早期介绍,其中描述了矿井通风和冷却要求的背景和规划,用于将矿井延伸至3100米。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号