首页> 外文会议>European Conference on Applied Superconductivity >Long-term test of the 22.9kV HTS power cable system in LS Cable Ltd.
【24h】

Long-term test of the 22.9kV HTS power cable system in LS Cable Ltd.

机译:LS电缆有限公司22.9kV HTS电力电缆系统的长期试验

获取原文

摘要

Since 2001, LS cable Ltd. has been developing the design, manufacturing and evaluation technologies for high temperature superconducting (HTS) power cable system as a member of DAPAS (Dream for Advanced Power system by Applied Superconductivity technology) program in Korea. The 30 m HTS cable system that is rated at 22.9 kV and 1.2 kA giving a rated capacity of 50 MVA had been developed and tested. The cable was designed as a cold dielectric type employing Bi-2223 HTS tapes and polypropylene (PP) laminated paper as the conductor and electrical insulation, respectively. The cable is cooled with sub-cooled liquid nitrogen at temperature from 75 to 77 K. The manufacturing and the installation of the cable system were completed in 2004. Long-term performance test of the cable system has been conducted for six months to verify its electric and mechanical properties in 2005.
机译:自2001年以来,LS电缆有限公司一直在开发高温超导(HTS)电力电缆系统的设计,制造和评估技术,作为DAPAS的成员(通过应用超导技术通过应用超导技术的梦想)。已经开发并测试了30米HTS电缆系统,其额定为22.9 kV和1.2 ka提供50 mVA的额定容量。电缆设计为使用Bi-2223 HTS胶带和聚丙烯(PP)层压纸作为导体和电绝缘的冷介质型。电缆在75至77k的温度下用子冷却的液氮冷却。电缆系统的制造和安装于2004年。电缆系统的长期性能测试已经进行了六个月才能验证其2005年电动和机械性能。