首页> 外文会议>WSEAS International Conferences >Based on Simple Four Conductors Model Measuring Distributed Parameters of 500kV Power Transformer Winding
【24h】

Based on Simple Four Conductors Model Measuring Distributed Parameters of 500kV Power Transformer Winding

机译:基于简单的四个导线模型测量500kV电力变压器绕组的分布式参数

获取原文

摘要

To analyze the propagation characteristic of high frequency signals, such as partial discharge (PD) in power transformer winding, it is necessary to determine the distributed parameters at high frequency of the power transformer winding. This paper discusses an experimental method for measuring the distributed parameters of the power transformer winding. The proposed experimental method only involves the input impedance measurements for the short- and open-circuit tests and then, the distributed parameters can be computed by formula. At last, the finite element method is used to compute the capacitance parameters of the power transformer winding. It indicates that the relative error between the calculational results and the experimental results is less than 20 percent. Thus the experimental method presented in this paper is demonstrated to be effective.
机译:为了分析电力变压器绕组中的局部放电(Pd)等高频信号的传播特性,需要确定电力变压器绕组的高频处的分布式参数。本文讨论了测量电力变压器绕组分布参数的实验方法。所提出的实验方法仅涉及短路和开路测试的输入阻抗测量,然后,可以通过公式计算分布式参数。最后,有限元方法用于计算电力变压器绕组的电容参数。它表明计算结果与实验结果之间的相对误差小于20%。因此,本文提出的实验方法被证明是有效的。