Grounding and ground fault protection of multiple generator installations on medium-voltage industrial and commercial power systems. Part 1 - the problem defined

机译:中压工业电力系统多发电机装置的接地和接地故障保护。第1部分 - 所定义的问题

获取原文

摘要

The paper discusses typical grounding practices and ground fault protection methods for medium-voltage generator stators, highlighting their merits and drawbacks. Particular attention is given to applications of multiple generators connected to a single bus. The paper also provides an overview of the generator damage mechanism during stator ground faults. Problem areas associated with each type of grounding are identified and solutions are discussed. The paper also provides a list of references on the topic. The paper is intended as a guide to aid engineers in selecting adequate grounding and ground fault protection schemes for medium-voltage industrial and commercial generators for new installations, for evaluating existing systems, and for future expansion of facilities, to minimize generator damage from stator ground faults.
机译:本文讨论了中压发电机定子的典型接地实践和接地故障保护方法,突出了它们的优点和缺点。特别注意多个发电机连接到单个总线的应用。本文还提供了定子接地故障期间发电机损坏机制的概述。鉴定了与每种接地相关的问题区域,并讨论了解决方案。本文还提供了关于该主题的引用列表。本文旨在辅助工程师在为新安装中选择适当的接地和地面故障保护方案,用于评估现有系统,以及为了将未来的设施扩大,以最大限度地减少定子地面的发电机损坏缺点。