Evaluation of the Grounding Circuit Measurements for Stator Ground-Fault Location of Synchronous Generators

机译:同步发电机定子接地故障位置的接地电路测量评估

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Locating stator-winding ground faults accurately is a very difficult task. In this paper the grounding circuit measurements are evaluated in order to obtain information about the stator ground-fault location in synchronous generators. In power generators grounded through a high impedance, the relation between the neutral voltage and the phase voltage provide a first estimation of the fault location. The location error by using this ratio depends on the fault resistance and the value of the capacitance to ground of the stator winding. However, the error added by ignoring the value of the fault resistance is the most relevant term. This location estimation and the location error have been evaluated through the data of a real synchronous machine.
机译:准确定位定子绕组接地故障是一项非常艰巨的任务。在本文中,对接地电路的测量进行了评估,以便获得有关同步发电机中定子接地故障位置的信息。在通过高阻抗接地的发电机中,中性点电压和相电压之间的关系提供了故障位置的第一估计。通过使用该比率的位置误差取决于故障电阻和定子绕组对地电容的值。但是,忽略故障电阻值而增加的误差是最相关的术语。该位置估计和位置误差已通过实际同步电机的数据进行了评估。