首页> 外文会议>European Conference on Applied Superconductivity >Long term operation in 200 m class superconducting DC power transmission test facility in Chubu University
【24h】

Long term operation in 200 m class superconducting DC power transmission test facility in Chubu University

机译:楚武大学200米级超导直流电力传动试验设施的长期运行

获取原文

摘要

We constructed the 200 m class superconducting DC power transmission test facility (CASER-2) in 2010, and have carried out the cooling down and operation test. The 5th cooling down and operation test was carried out from August to November 2012. Long term current feeding was tested for a month with various currents and temperatures in the 5th test. From the long term current feeding test, the LN2 circulation was clearly affected by the operation of the cryogenic system and the atmosphere, not only by the operation DC current. It was also confirmed that the Peltier current leads worked effectively for the reduction of heat leak at the cable terminal.
机译:我们在2010年构建了200米级超导直流电力传输测试设施(CASER-2),并进行了冷却和操作测试。 5日冷却和操作试验从8月到2012年11月进行。在第5次试验中测试了长期电流喂养,并在第5次测试中进行了各种电流和温度。从长期电流馈电测试,LN2循环通过低温系统和气氛的操作显然影响,不仅通过操作DC电流。还证实了珀耳帖电流引线有效地用于减少电缆端子的热泄漏。