A wide sidewall return cleanroom designed with insufficient length of sidewall return air grilles was examined. The cleanroom was extremely hard, almost impossible, to be balanced to required laminarity level due to its wide span and insufficient space length of return air grilles. Computational Fluid Dynamics (CFD) technique was used to examine the airflow patterns in the cleanroom. The analysis results were used to guide the remodeling effort. A significant improvement on laminarity was achieved in the modification project.
机译:检查了侧壁返回洁净室的宽侧壁净空,侧壁返回空气格栅长度不足。洁净室非常坚硬,几乎是不可能的,由于其宽跨度和空间长度的空间长度而被平衡到所需的层状水平。计算流体动力学(CFD)技术用于检查洁净室中的气流图案。分析结果用于指导重塑努力。在改性项目中实现了对层状的显着改善。