Effects of Voltage Sags on Three-phase Three-legged Transformers

机译:电压凹陷在三相三腿变压器上的影响

获取原文

摘要

This paper describes the influence of voltage sags on three-phase three-legged transformers. The model includes saturation, and it is based on experimental parameters. It has been implemented in PSpice. Voltage recovery after the voltage sag causes transformer saturation. This saturation produces an inrush current similar to that of the transformer energizing. The variables that influence the peak value of the inrush current are studied: depth, duration and initial point-on-wave. The most important variable is sag duration, which has a periodical influence.
机译:本文介绍了电压凹陷对三相三腿变压器的影响。该模型包括饱和度,并且基于实验参数。它已在pspice中实施。电压凹槽后的电压恢复导致变压器饱和度。该饱和度产生类似于变压器通电的浪涌电流。研究了影响浪涌电流的峰值的变量:深度,持续时间和初始点波。最重要的变量是下垂的持续时间,其具有期刊影响。